Before installation and use, be sure to read the installation & Operation Manual carefully.
The product should be used correctly under the following conditions:
• Ambient temperature: 10~45℃;
• Atmospheric pressure: 86kPa~106kPa;
• Water supply needs to be softened, water supply temperature <45℃, water supply pressure: 0.15~0.6MPa;
• Voltage deviation does not exceed ± 5% of rated voltage;
• The ambient air quality should meet the GB 3098 Level 3 or above standard.
• Install the controller and signal line away from strong magnetic interference.
• The air cooler must be installed in a ventilated and dry location to ensure that the air cooler sucks in 100% of outdoor fresh air.
• To ensure the best effect of this machine, ensure that there are enough doors or windows open.
• During the installation and use of the air cooler, be careful not to allow welding sparks or other ignition sources to be close to the air cooler unit.
• When installing the power supply, choose and install the wire according to the requirements of the national standard, and be sure to ground the wire.
The product should be used correctly under the following conditions:
• Ambient temperature: 10~45℃;
• Atmospheric pressure: 86kPa~106kPa;
• Water supply needs to be softened, water supply temperature <45℃, water supply pressure: 0.15~0.6MPa;
• Voltage deviation does not exceed ± 5% of rated voltage;
• The ambient air quality should meet the GB 3098 Level 3 or above standard.
• Install the controller and signal line away from strong magnetic interference.
• The air cooler must be installed in a ventilated and dry location to ensure that the air cooler sucks in 100% of outdoor fresh air.
• To ensure the best effect of this machine, ensure that there are enough doors or windows open.
• During the installation and use of the air cooler, be careful not to allow welding sparks or other ignition sources to be close to the air cooler unit.
• When installing the power supply, choose and install the wire according to the requirements of the national standard, and be sure to ground the wire.
The Evaporative Air Coolers are efficient, environment-friendly and energy saving products, which will provide you with the comfort environment and fresh air. The products work based on the principle of evaporative cooling and use high efficiency cooling pads as evaporation media. The fan relies at through the evaporative cooling pads, water driven by the pump circulates from top to bottom of evaporative pads. Heat is supplied by air to water which cause water evaporation and air cooling, water is added automatically as the water level inside the tank falls below the minimum level.
Defined number of ventilation:
• The general environment requirement is 25~30 times an exchange / hour
• In crowded toilet places, use air exchange plus 30~40 times a hour
• In places or production workshops with dense crowds and high temperature, 40-50 times / hour air change is required;
• High temperature and severely polished production workshops require 50-60 air changes per hour.
• In severe high humidity area, air exchange rate should be higher than standards.
• The general environment requirement is 25~30 times an exchange / hour
• In crowded toilet places, use air exchange plus 30~40 times a hour
• In places or production workshops with dense crowds and high temperature, 40-50 times / hour air change is required;
• High temperature and severely polished production workshops require 50-60 air changes per hour.
• In severe high humidity area, air exchange rate should be higher than standards.